Rhoss Water Chiller Unit — Real-time power, energy and alarm monitoring via Modbus RTU protocol with 6S Teknoloji.
Connect the device to the RS-485 or Ethernet network. Configure Slave ID and baud rate from the device front panel or web interface.
From the 6S web panel click "New Device". Select Rhoss Chiller from the template list — the register map loads automatically.
The Field Agent tests the connection; the first readings appear on the dashboard shortly. Alarm thresholds are configured.
Under the same brand, different controller families use different address layouts and scaling. Applying one family's map to another yields zeros, -99.99 or physically impossible values; when writing a setpoint it risks the wrong register or the wrong scale (0.8 °C instead of 8 °C). 6S Teknoloji first reads the HR201 (application ID) and HR202 (software version) identity pair on every unit and selects the map accordingly.
| Controller | Identity (HR201/HR202) | Key difference |
|---|---|---|
| FPV33 | Software 6.7 | Extensive register + coil map; capacity in per-mille scale (1000 = 100%) |
| Z-POWER | 12 / 59 → software 5.9 | Address layout differs from FPV33; the FPV33 map is invalid on this unit |
| FW 9.4 | 12 / 94 → software 9.4 | Mixed scaling: water temperature and setpoint ×0.01, refrigerant side ×0.1 |
| GZ COMPACT | 0 / 0 → identity not readable | Smaller controller; the set point sits in a different register, only measurement-verified points are published |
The Rhoss integration is at its strongest with rule-based night mode and energy correlation. Details on the chiller optimisation solution page.