An X/5 meter is an electricity meter that measures current through a current transformer rather than directly. "X" is the primary current and "5" the standard 5 A that flows from the transformer secondary to the meter: 100/5, 200/5, 400/5 and so on. Almost every facility whose load current exceeds 100 A meters this way. This article explains how X/5 meter wiring is done, which terminals a three-phase meter wiring diagram includes, how the multiplier is calculated and which mistakes are most common in the field.
The current inputs of meters and analysers are generally designed for 5 A (1 A on some models). Passing the 630 A of a main switchboard directly through a meter is not possible. A current transformer (CT) scales the primary current down at a fixed ratio: in a 400/5 A CT, 400 A on the primary produces 5 A on the secondary. The meter measures 5 A and the ratio is applied to obtain the real value. Direct-connected meters are typically used for loads between 5 and 100 A.
| Connection | Terminal | Description |
|---|---|---|
| Voltage inputs | L1, L2, L3, N | Phase-to-neutral voltages, directly or via fuses |
| Current input L1 | S1 → in, S2 → out | Secondary of the CT on phase L1 |
| Current input L2 | S1 → in, S2 → out | Secondary of the CT on phase L2 |
| Current input L3 | S1 → in, S2 → out | Secondary of the CT on phase L3 |
| Earthing | S2 common point | Secondary circuit earthed at one point |
| Communication | A/B (RS-485) | Remote reading over Modbus RTU |
The CT's P1 terminal must face the supply side and P2 the load side. Which meter input the S1 and S2 secondary leads reach determines the direction of measurement. Phase order is equally critical: the L1 voltage and the L1 current transformer must be on the same phase; otherwise the meter sees a wrong power factor and under-counts or even negatively counts energy.
At commissioning, read current, voltage, active power and power factor for each phase separately. In a healthy connection all three phases show positive active power and a power factor consistent with the load (e.g. 0.8–0.95 inductive for motor loads). If one phase has negative power or a power factor very different from the others, check that phase's CT direction or phase pairing. A power analyser's phasor diagram screen completes this check in minutes; see what is a power analyser.
Wiring errors are usually discovered not at commissioning but months later, when the bill and the meter disagree. While reading meters and analysers over Modbus, the 6S Teknoloji platform watches active power per phase; when negative power or an inconsistent power factor appears, it raises a wiring-error alarm and opens a field correction request instead of hiding the value. The multiplier is defined once in the device template, so a CT replaced in the panel is updated in software too. See the electricity monitoring page and the Schneider PM5350 template among supported devices.