Power factor correction (called "kompanzasyon", compensation, in Turkish) is the practice of supplying a facility's reactive power locally so that it is no longer drawn from the grid, thereby correcting the power factor. The inductive reactive power needed by motors and transformers is provided by capacitors installed in a panel; only the active power that does real work is drawn from the grid. This article explains what compensation means, what PFC capacitors and capacitor contactors do and how the reactive power controller makes its decisions, in plain language.
Coil-based (inductive) loads such as motors, transformers, ballasts and welding machines continuously take energy from the grid and return it to build their magnetic fields. This back-and-forth energy does no work, yet it loads cables and transformers. It is called inductive reactive power (kVAr). The vector sum of active power (kW) and reactive power is apparent power (kVA); the ratio of active to apparent power is the power factor (cos φ). The lower the power factor, the more current is drawn for the same work.
A capacitor behaves opposite to a coil: while inductive load current lags the voltage, capacitor current leads it. When both meet in the same panel, their reactive currents largely cancel. The reactive power measured on the grid side approaches zero and the power factor approaches 1. Capacitors are grouped into steps (e.g. 5, 10, 20 kVAr) and switched in and out according to the load.
| Element | Function | Watch out |
|---|---|---|
| PFC capacitor | Produces capacitive reactive power | Voltage and kVAr rating matched to the load; life shortened by heat and harmonics |
| Capacitor contactor | Switches a step in/out | Use capacitor-duty type with pre-charge resistors |
| Reactive power controller | Measures and decides on steps | CT must be at the main incomer; wrong CT = wrong decisions |
| Shunt reactor | Balances capacitive excess | For sites at risk of capacitive penalty at night / low load |
| Detuning reactor | Protects capacitors from harmonics | Mandatory in drive- and UPS-heavy facilities |
| Fuse / breaker | Step protection | Sized for 1.5 × rated capacitor current |
A PFC panel may look as if it is working while the problem only surfaces as a penalty on the bill. The 6S Teknoloji platform reads the reactive power controller and the main meter over Modbus, calculates the inductive and capacitive reactive ratios hourly and sends alerts when the penalty limit is approached or a step fault is suspected. Corrections are made daily instead of paying monthly penalties. See the power factor correction monitoring solution page and the GrupArge RKR template among supported controllers.