Power factor correction (called "kompanzasyon", compensation, in Turkish) is the practice of supplying a facility's reactive power locally so that it is no longer drawn from the grid, thereby correcting the power factor. The inductive reactive power needed by motors and transformers is provided by capacitors installed in a panel; only the active power that does real work is drawn from the grid. This article explains what compensation means, what PFC capacitors and capacitor contactors do and how the reactive power controller makes its decisions, in plain language.

Why does reactive power arise?

Coil-based (inductive) loads such as motors, transformers, ballasts and welding machines continuously take energy from the grid and return it to build their magnetic fields. This back-and-forth energy does no work, yet it loads cables and transformers. It is called inductive reactive power (kVAr). The vector sum of active power (kW) and reactive power is apparent power (kVA); the ratio of active to apparent power is the power factor (cos φ). The lower the power factor, the more current is drawn for the same work.

How does correction work?

A capacitor behaves opposite to a coil: while inductive load current lags the voltage, capacitor current leads it. When both meet in the same panel, their reactive currents largely cancel. The reactive power measured on the grid side approaches zero and the power factor approaches 1. Capacitors are grouped into steps (e.g. 5, 10, 20 kVAr) and switched in and out according to the load.

Parts of a PFC panel

ElementFunctionWatch out
PFC capacitorProduces capacitive reactive powerVoltage and kVAr rating matched to the load; life shortened by heat and harmonics
Capacitor contactorSwitches a step in/outUse capacitor-duty type with pre-charge resistors
Reactive power controllerMeasures and decides on stepsCT must be at the main incomer; wrong CT = wrong decisions
Shunt reactorBalances capacitive excessFor sites at risk of capacitive penalty at night / low load
Detuning reactorProtects capacitors from harmonicsMandatory in drive- and UPS-heavy facilities
Fuse / breakerStep protectionSized for 1.5 × rated capacitor current

Why is it considered mandatory?

  • Reactive penalty: in Türkiye, customers above a certain power threshold pay a penalty when inductive or capacitive reactive energy exceeds a set ratio of active energy. See our reactive energy penalty article.
  • Capacity: raising the power factor from 0.7 to 0.95 lets the same transformer carry roughly 35% more active load.
  • Losses: lower current means lower copper losses in cables and transformers and better voltage regulation.

Common problems in PFC panels

  • Capacitor capacitance degrades over time; the controller switches a step but the kVAr does not arrive and penalties begin.
  • Contactor contacts weld or fail to open; a step stays in at night with no load and a capacitive penalty results.
  • The controller's CT is on the wrong phase or reversed; the controller keeps making wrong decisions.
  • Harmonic distortion is high; capacitors overheat, bulge and blow fuses.
  • Too few steps; fine adjustment is impossible and the ratio oscillates around the limit.

Monitoring power factor correction remotely

A PFC panel may look as if it is working while the problem only surfaces as a penalty on the bill. The 6S Teknoloji platform reads the reactive power controller and the main meter over Modbus, calculates the inductive and capacitive reactive ratios hourly and sends alerts when the penalty limit is approached or a step fault is suspected. Corrections are made daily instead of paying monthly penalties. See the power factor correction monitoring solution page and the GrupArge RKR template among supported controllers.

Related Content

Compensation Panel Monitoring — RKRWhat Is a Reactive Energy Penalty? 2026 RatesGrupArge RKR Reactive Relay Integrationenergy monitoring systemreactive penalty preventiontransformer load and temperature monitoringPower Factor Panel Maintenance: A ChecklistWhat Is kVA? kVA to kW Conversion Explained

FAQ

What does power factor correction mean in short?
Supplying the reactive power needed by motors and transformers from capacitors in the panel instead of drawing it from the grid, bringing the power factor close to 1. The aims are avoiding reactive penalties, freeing transformer capacity and reducing losses.
What is the difference between a capacitor contactor and a standard contactor?
A capacitor draws a very high inrush current when switched in. Capacitor-duty contactors have auxiliary contacts with pre-charge resistors that limit this inrush; a standard contactor's contacts weld quickly.
Why do we still get a reactive penalty with a PFC panel?
The most common causes are degraded capacitors, welded or stuck contactors, a wrongly wired controller CT and steps left in at night under low load causing a capacitive penalty. Continuous monitoring of the reactive ratio reveals these before the bill arrives.