What Is Power Factor (cos φ)? Reactive Power and the Power Triangle

6S Teknoloji · 08.11.2026 · 6 min read

What Is Power Factor (cos φ)? Reactive Power and the Power Triangle — 6S Teknoloji

Power factor (cos φ) is the ratio showing how much of the power a facility draws from the grid is actually turned into useful work. 1.00 is ideal; 0.80 means only 80 percent of the power drawn does work, while the rest oscillates to build magnetic fields. This article explains what power factor is, what reactive power is, how to calculate cos φ, what inductive and capacitive mean, and what a low power factor costs a facility, in plain language.

Active, reactive and apparent power

In alternating current, voltage and current do not always peak at the same moment. Coil-based loads such as motors, transformers and ballasts shift the current behind the voltage. The angle of that shift is φ, and power splits into three components:

PowerSymbol / unitWhat it doesRelation to the bill
Active powerP, kWDoes work: turns motors, heats, lightsBilled as kWh
Reactive powerQ, kVArBuilds and collapses magnetic fields; does no work, loads the linesPenalty charge if the ratio limit is exceeded
Apparent powerS, kVAVector sum of the two; sets transformer and line capacityContracted capacity, demand

In the power triangle S is the hypotenuse, P and Q are the legs. Power factor: cos φ = P ÷ S. The same relation gives tan φ = Q ÷ P; in Türkiye reactive penalty limits are defined on this ratio, with separate thresholds for inductive and capacitive.

How to calculate power factor

  1. From instantaneous values: if the analyser reads kW and kVA, cos φ = kW ÷ kVA. Example: 85 kW and 100 kVA → 0.85.
  2. From energy values (monthly average): take the kWh and kVArh differences; tan φ = kVArh ÷ kWh, cos φ = 1 ÷ √(1 + tan² φ). Example: 50,000 kWh and 25,000 kVArh → tan φ = 0.50 → cos φ ≈ 0.89.
  3. From measurement: single phase P = U × I × cos φ, so cos φ = P ÷ (U × I); for three phase the denominator is √3 × U(line) × I.

An important distinction: the monthly average cos φ computed from the meter and the instantaneous cos φ shown by the analyser are different things. The penalty is based on the monthly energy ratio; instantaneous values show at which hour and under which load the problem arises.

Inductive and capacitive power factor

  • Inductive (lagging): current lags the voltage. Motors, transformers, welding machines, old fluorescent ballasts. Remedy: add capacitors.
  • Capacitive (leading): current leads the voltage. Long cables, excess capacitors, correction running at low load, drive and UPS input filters. Remedy: smaller steps or a shunt reactor.
  • Exceeding the limit in either direction is penalised; monitoring inductive alone is not enough. Capacitive overshoot at night and weekends under low load is the most common trap.

What does a low power factor cost?

  • Reactive penalty: when the inductive or capacitive ratio limit is exceeded, a separate charge appears on the bill.
  • Lost capacity: a 400 kVA transformer carries 320 kW at cos φ 0.80 and 392 kW at 0.98; the difference is the price of a new transformer.
  • Line losses: more current flows for the same kW; losses grow with the square of current. Going from 0.80 to 1.00 cuts current by 20 percent at the same load and copper losses by roughly 36 percent.
  • Voltage drop: high current drops voltage on long runs; motors overheat, lighting flickers.

How to improve and monitor power factor

The classic remedy is a stepped capacitor panel managed by a reactive power controller (power factor correction). Having the panel is not enough: when a contactor welds, a capacitor loses capacitance or the controller setting drifts, the penalty quietly returns. Good practice is therefore to ratio the inductive and capacitive reactive energy at the main meter against kWh every day and raise an alert as the threshold approaches. If the problem is seen before the monthly bill arrives, the fix happens within the same month and no penalty accrues.

Summary

Power factor is the share of drawn power that becomes useful work; cos φ = kW ÷ kVA. Reactive power does no work but loads lines and transformers and triggers a penalty when the limit is exceeded. Inductive overshoot is fixed with capacitors, capacitive overshoot with smaller steps or reactors. A system that tracks the ratio daily rather than monthly catches a correction fault before the penalty reaches the bill.

Related Content

What Is a Reactive Energy Penalty? 2026 RatesCompensation Panel Monitoring — RKRWhat Is an Energy Analyzer? Buyer's Guideenergy monitoring and management systemreactive penalty trackingtransformer monitoring softwareWhat Are Harmonics? THD and Its EffectsPassive vs Active Harmonic Filter Selection

FAQ

What is power factor (cos φ)?
The ratio of active power to apparent power: cos φ = kW ÷ kVA. 1.00 is ideal; 0.80 means only 80 percent of the power drawn does work. It is the cosine of the phase angle between voltage and current.
What is reactive power and why is it penalised?
It is the power (kVAr) that oscillates between grid and load to magnetise motors and transformers without doing work. It loads lines and transformers unnecessarily; when monthly reactive energy exceeds the allowed ratio to active energy, a reactive charge is added to the bill.
What is the difference between inductive and capacitive power factor?
Inductive: current lags the voltage (motors, transformers); the remedy is capacitors. Capacitive: current leads (long cables, excess capacitors, low load); the remedy is smaller steps or a shunt reactor. Exceeding the limit in either direction is penalised.