6S Teknoloji · 16.11.2026 · 6 min read
The most common way to compare buildings of different sizes in a single table is energy use intensity: the energy consumed over a given period divided by floor area, expressed in kWh/m². For a portfolio manager, this indicator shows at a glance which facility uses its resources more efficiently; for an energy manager, it is the starting point for setting improvement priorities. But if the numerator and denominator are defined differently from site to site, and if climate and occupancy differences are ignored, the ranking stops being a guide and starts driving the wrong decisions. This article walks through how energy intensity is calculated, which corrections it needs, and how to make a benchmark defensible.
The basic formula is simple: EUI = E / A, where E is energy consumption over the chosen period (kWh) and A is the defined building area (m²). Energy Use Intensity (EUI) is one of the best-known energy performance indicators (EnPIs) used under ISO 50001. Three decisions should be settled before you start:
The most frequent mistake in intensity benchmarking is placing different area definitions side by side. When the gross floor area from one site's architectural drawings is compared with another site's net usable area, the ranking reflects a measurement difference rather than building efficiency.
| Area definition | What it covers | What to watch |
|---|---|---|
| Gross floor area | All floors measured to the outside face of external walls | Including car parks and plant floors makes intensity look lower than it really is |
| Net usable area | Usable interior spaces | Whether common areas are included varies between sites |
| Heated or conditioned area | Floor area of actively conditioned spaces | The most meaningful denominator for heating and cooling intensity |
Choose one definition for the entire portfolio, write it down, and enter every site's area under the same rule. Noting high-intensity spaces such as enclosed car parks, server rooms or commercial kitchens separately makes deviations much easier to interpret.
The numerator has to be right as well. Data quality issues that come up frequently in the field include:
Two buildings with identical insulation and operating quality will show different heating consumption if one sits in a mild coastal city and the other in a cold inland region. The same difference appears between a cold winter and a mild one in the same building. Heating degree days (HDD) remove this effect: for each day HDD = max(0, T_base − T_avg) is calculated and summed over the period. Normalized intensity is then expressed as E_season / (A × ΣHDD), giving energy per unit area per degree day.
Normalization only makes sense for weather-sensitive consumption. Base loads such as domestic hot water, kitchens and lighting do not depend on outdoor temperature, so it is more accurate to restrict the window to the heating season or to separate consumption by regression into a base load plus a degree-day slope. ISO 50006 describes this kind of relevant-variable adjustment for energy performance indicators and baselines. If weather data has missing days, the normalized value loses reliability, and sites with insufficient coverage should be left out of the comparison. Cooling-dominated buildings follow the same logic using cooling degree days (CDD).
Climate is not the only variable. A hospital that runs around the clock and an office that operates during weekday business hours cannot share the same intensity, even with equal floor area. Benchmarks should therefore be grouped by sector and operating profile first, with a second normalization by occupancy indicators such as occupied beds, guest nights or operating hours where needed.
In Türkiye, the Energy Performance Certificate issued under the Regulation on Energy Performance of Buildings rates a building against a reference building. The certificate relies on a calculation with standard usage assumptions, whereas metered operational intensity reflects actual behavior. The two complement each other, but neither replaces the other: a well-rated building that is poorly operated can still show high operational intensity.
6S Teknoloji applies a large part of these rules in its calculation layer. On the multi-site comparison screen, each facility's monthly electricity consumption is divided by its registered floor area and displayed side by side in kWh/m², color-coded by sector. The natural gas portfolio view provides a month-to-date kWh/m² ranking, a median reference line, the most efficient site and each site's rank change against the same day window last month, while the portfolio average is weighted by dividing total consumption by total area. A degree-day normalized league is also produced for the last heating season: seasonal consumption is divided by area and total HDD, weather data comes from the Open-Meteo archive for each project location, and sites with insufficient day coverage are excluded from the league.
On the methodology side, the electricity site total is taken from the main source, meaning the transformer or main meter; because sub-meters are not added to that total, double counting cannot occur. Electricity, water and natural gas are resolved separately, so data from one carrier never leaks into another carrier's indicator. The intensity ranking therefore highlights real operating differences between sites instead of measurement artifacts.