📝 Hardware

How to Read an Electricity Meter: Index, Tariff Registers and Multiplier

6S Teknoloji · 08.11.2026 · 6 min read

How to Read an Electricity Meter: Index, Tariff Registers and Multiplier — 6S Teknoloji

Reading your electricity meter is the first step toward understanding the bill and controlling consumption. This guide explains what a meter index is, what the rotating display codes 1.8.0 / 1.8.1 / 1.8.2 mean, and how the multiplier works on meters connected through current transformers. The method is the same from a household meter to a factory main meter; only the number of registers and the multiplier change.

What is a meter index?

An electricity meter accumulates the energy drawn from the grid in kilowatt-hours (kWh). The large number on the display is the index: total energy since the meter was installed. The index never resets; it only grows. Consumption is the difference between two indexes. The meter does not tell you "what you used this month"; you (or the utility) take two readings and subtract.

Display codes: 1.8.0, 1.8.1, 1.8.2, 1.8.3

Electronic meters cycle through a series of registers every few seconds. The codes follow the OBIS standard. The most common ones are:

CodeMeaningUsed for
1.8.0Total active energy index (kWh)Single-rate tariff, total check
1.8.1T1 daytime register (06:00–17:00 in Türkiye)Time-of-use tariff
1.8.2T2 peak register (17:00–22:00)Time-of-use tariff
1.8.3T3 night register (22:00–06:00)Time-of-use tariff
5.8.0Inductive reactive energy (kVArh)Reactive penalty tracking
8.8.0Capacitive reactive energy (kVArh)Reactive penalty tracking
1.6.0Maximum demand in the period (kW)Demand limit check

A simple rule: 1.8.1 + 1.8.2 + 1.8.3 must equal 1.8.0. If it does not, the meter is configured single-rate or the reading is wrong.

Single-rate versus time-of-use reading

On a single-rate tariff only the 1.8.0 index goes to the bill. On a time-of-use tariff, T1, T2 and T3 are read separately and each is multiplied by its own unit price. See our time-of-use tariff article for the time bands and selection rules. Looking only at 1.8.0 without knowing your tariff hides the cost that accumulates during peak hours.

Multiplier: meters fed by current transformers (x/5)

In larger facilities the meter does not measure current directly but through a current transformer (CT). With a 200/5 A transformer the displayed index must be multiplied by 40 (200 ÷ 5 = 40). Some meters store the ratio internally and show the real value; others show the raw value and the multiplier is applied on the bill. Always check the "multiplier" field on the meter label or the supply contract. A wrong multiplier produces months of under- or over-billing.

Step-by-step consumption calculation (example)

  • Index at start of month (1.8.0): 48,210 kWh
  • Index at end of month (1.8.0): 51,790 kWh
  • Difference: 51,790 − 48,210 = 3,580 kWh
  • Multiplier 1 → 3,580 kWh; multiplier 40 → 143,200 kWh

On a time-of-use meter you repeat the same subtraction for 1.8.1, 1.8.2 and 1.8.3. The numbers are illustrative; use your own meter's index.

Mechanical versus electronic meters

Older mechanical meters have a rotating disc and a mechanical counter; only the total index is read and the decimal digit (usually red) is ignored on the bill. Electronic meters show coded registers in sequence on an LCD and most can be read remotely over an optical port or RS-485.

Automating meter reading

A manual reading once a month cannot show which day or hour drove consumption up. The 6S Teknoloji energy monitoring platform reads meters and analysers over Modbus or M-Bus, computes the index difference hourly and daily, and shows the T1-T2-T3 split and the reactive ratio on one screen. With several meters, the main meter is automatically reconciled against the sum of sub-meters, and a growing gap raises an alert. Meter reading turns from a monthly estimate into daily manageable data. See the electricity monitoring and main meter monitoring solution pages for details.

Related Content

Multi-Time Tariff (T1/T2/T3) ExplainedElectricity Consumption MonitoringMain Meter Monitoring — Time-of-Useenergy monitoring softwarereactive penalty preventiontransformer load and temperature monitoringWhat Is an Energy Analyzer? Buyer's GuideEnergy Audit Report: Contents and Process

FAQ

What does 1.8.0 mean on an electricity meter?
1.8.0 is the total active energy index in kWh since installation. On time-of-use meters it equals the sum of 1.8.1 (day), 1.8.2 (peak) and 1.8.3 (night).
What is the meter multiplier and where do I find it?
On CT-connected meters the display shows a raw value; the real consumption is the display multiplied by the CT ratio (e.g. 200/5 = 40). The multiplier is printed on the meter label, in the supply contract or on the bill.
How do I get consumption from two readings?
Subtract the start-of-period index from the end-of-period index and multiply by the multiplier, e.g. 51,790 − 48,210 = 3,580 kWh. Repeat for the T1, T2 and T3 registers on time-of-use meters.