Reading your electricity meter is the first step toward understanding the bill and controlling consumption. This guide explains what a meter index is, what the rotating display codes 1.8.0 / 1.8.1 / 1.8.2 mean, and how the multiplier works on meters connected through current transformers. The method is the same from a household meter to a factory main meter; only the number of registers and the multiplier change.
An electricity meter accumulates the energy drawn from the grid in kilowatt-hours (kWh). The large number on the display is the index: total energy since the meter was installed. The index never resets; it only grows. Consumption is the difference between two indexes. The meter does not tell you "what you used this month"; you (or the utility) take two readings and subtract.
Electronic meters cycle through a series of registers every few seconds. The codes follow the OBIS standard. The most common ones are:
| Code | Meaning | Used for |
|---|---|---|
| 1.8.0 | Total active energy index (kWh) | Single-rate tariff, total check |
| 1.8.1 | T1 daytime register (06:00–17:00 in Türkiye) | Time-of-use tariff |
| 1.8.2 | T2 peak register (17:00–22:00) | Time-of-use tariff |
| 1.8.3 | T3 night register (22:00–06:00) | Time-of-use tariff |
| 5.8.0 | Inductive reactive energy (kVArh) | Reactive penalty tracking |
| 8.8.0 | Capacitive reactive energy (kVArh) | Reactive penalty tracking |
| 1.6.0 | Maximum demand in the period (kW) | Demand limit check |
A simple rule: 1.8.1 + 1.8.2 + 1.8.3 must equal 1.8.0. If it does not, the meter is configured single-rate or the reading is wrong.
On a single-rate tariff only the 1.8.0 index goes to the bill. On a time-of-use tariff, T1, T2 and T3 are read separately and each is multiplied by its own unit price. See our time-of-use tariff article for the time bands and selection rules. Looking only at 1.8.0 without knowing your tariff hides the cost that accumulates during peak hours.
In larger facilities the meter does not measure current directly but through a current transformer (CT). With a 200/5 A transformer the displayed index must be multiplied by 40 (200 ÷ 5 = 40). Some meters store the ratio internally and show the real value; others show the raw value and the multiplier is applied on the bill. Always check the "multiplier" field on the meter label or the supply contract. A wrong multiplier produces months of under- or over-billing.
On a time-of-use meter you repeat the same subtraction for 1.8.1, 1.8.2 and 1.8.3. The numbers are illustrative; use your own meter's index.
Older mechanical meters have a rotating disc and a mechanical counter; only the total index is read and the decimal digit (usually red) is ignored on the bill. Electronic meters show coded registers in sequence on an LCD and most can be read remotely over an optical port or RS-485.
A manual reading once a month cannot show which day or hour drove consumption up. The 6S Teknoloji energy monitoring platform reads meters and analysers over Modbus or M-Bus, computes the index difference hourly and daily, and shows the T1-T2-T3 split and the reactive ratio on one screen. With several meters, the main meter is automatically reconciled against the sum of sub-meters, and a growing gap raises an alert. Meter reading turns from a monthly estimate into daily manageable data. See the electricity monitoring and main meter monitoring solution pages for details.